When modeling an HVAC system using fan powered terminal units with EnergyPlus, the user must enter values for fan total pressure rise and fan/motor efficiency. A recent study found that for an 8 inch inlet (203 mm) series fan powered terminal unit, the fan total pressure was considerably lower than values commonly recommended in online training sources. Values in that study were on the order of 0.25 in. w.g. (63 Pa) and not 1.5 or even as much as 3 in. w.g. (374 – 747 Pa). Manufacturer’s performance data were used to verify and extend VAV fan powered terminal unit total pressure rise measurements as determined in a previous study.