Technical Paper Session 6 Airside HVAC Advances

Wednesday, June 28, 2017: 11:00 AM-12:30 PM
HVAC&R Systems and Equipment
Chair: Ratnesh Tiwari, Ph.D., University of Maryland
This session covers research on airside HVAC systems. Presentations include using natural ventilation for healthcare applications, modeling fan terminal units, minimum airflow rates and energy recovery for labs.

1  Differential Pressure Rise Measurements and Impact in EnergyPlus Modeling for Series VAV Fan Powered Terminal Units Using PSC Motors (LB-17-016)

John Bryant, Ph.D., P.E., Texas A&M University
When modeling an HVAC system using fan powered terminal units with EnergyPlus, the user must enter values for fan total pressure rise and fan/motor efficiency. A recent study found that for an 8 inch inlet (203 mm) series fan powered terminal unit, the fan total pressure was considerably lower than values commonly recommended in online training sources. Values in that study were on the order of 0.25 in. w.g. (63 Pa) and not 1.5 or even as much as 3 in. w.g. (374 – 747 Pa). Manufacturer’s performance data were used to verify and extend VAV fan powered terminal unit total pressure rise measurements as determined in a previous study.

2  ASHRAE SSPC 170 Natural Ventilation Task Group: Position Paper on Natural Ventilation in Health Care Facilities (LB-17-017)

Travis English, P.E., Kaiser Permanente
Paul Ninomura, Indian Health Service
Heather Burpee, University of Washington Integrated Design Lab
Jeremy Fauber, P.E., Heapy Engineering
Arash Guilty, Mazzetti
The current version of ASHRAE Standard 170 procludes natural ventilation in all spaces in healthcare facilities. This work-group suggests it should be allowed in most healthcare spaces, except for Operating Rooms, Procedure Suites, Sterile Core areas, Interventional Radiology or Cardiology Spaces, Airborne Isolation Areas, and Protective Environments. Natural or mixed-mode ventilation designs may offer some benefits. Among the most likely are energy reduction and enhanced occupant satisfaction. Less likely benefits may include enhanced indoor air quality and a more beneficial microbiome. When considering natural ventilation in health care, designers must fully address the fundamental challenges of space appropriateness, climate appropriateness, acoustics, security, and outdoor air quality. Projects implementing natural ventilation should anticipate commissioning challenges.

3  Redesigning the HVAC System of a University Laboratory Building (LB-17-018)

James Mathias, Southern Illinois University Carbondale
Navya Madineedi, Southern Illinois University Carbondale
Justin Harrell, Southern Illinois University Carbondale
The energy consumption of the heating and cooling coils of the air handling units of an educational building with multiple laboratories has been evaluated and suitable energy recovery methods were assessed in an attempt to reuse the energy lost in the exhaust air stream and promote energy conservation while complying with the current building codes. The HVAC system of Life Sciences II (LS II) building of Southern Illinois University Carbondale, is a constant air volume (CAV), 100% outside air (OA) system due to the many laboratories in the building. It is one of the most energy intensive buildings on campus.

4  Energy and Control Performance Investigation of Air Handling Units with Return Air Bypass (LB-17-019)

Gang Wang, P.E., University of Miami
Xuejing Zheng, Tianjin University
Esber Andiroglu, University of Miami
Li Song, Ph.D., P.E., University of Oklahoma
The adoption of energy efficient standards significantly cut the energy consumption in buildings by reducing envelope heat transfer and internal heat gain. These energy efficiency measures reduce not only the electrical load but also the cooling load as well as the supply airflow rate. As a result, additional reheat is typically required to maintain the minimum airflow setpoint under partial space cooling loads for conventional air handling units (AHUs) and may degrade the effectiveness of energy efficient measures. The AHUs with return air bypass (RAB) provides an alternative to reduce additional reheating and overcooling at the minimum airflow rate with good space humidity control. The purpose of this paper is to investigate the energy and control performance of the AHUs with RAB under different operating conditions through simulations.

Register now!